Underground Distribution Cables
STANDARDS
National : CSA C22.2 N° 52
DESCRIPTION
Compact stranded AA-8000 series aluminum conductor material (ACM)
per ASTM B801 Class B or ASTM B836 (Single Input Wire), or aluminum
alloy 1350 per ASTM B400 Class B.
Black cross-linked polyethylene insulation
Colour-coded, flame retardant, sunlight resistant PVC jacket
Two phase conductors plus one full or reduced neutral conductor
CSA C22.2 No.52
Metric Units
Phase Conductor Size (AWG/ Kcmil) |
Neutral Conductor Size (AWG/ Kcmil) |
Insulation Thickness |
Jacket Thickness |
Approximate Diameter |
Linear Mass (Kg/Km) |
Phase (mm) |
Neutral (mm) |
Phase (mm) |
Neutral (mm) |
Phase (mm) |
Neutral (mm) |
Overall (mm) |
4 |
4 |
1.1 |
1.1 |
0.8 |
0.8 |
9.45 |
9.45 |
20.4 |
330 |
4 |
6 |
1.1 |
1.1 |
0.8 |
0.8 |
9.45 |
8.3 |
19.6 |
300 |
2 |
2 |
1.1 |
1.1 |
0.8 |
0.8 |
10.9 |
10.9 |
23.5 |
460 |
2 |
4 |
1.1 |
1.1 |
0.8 |
0.8 |
10.9 |
9.45 |
22.5 |
415 |
1 |
1 |
1.4 |
1.4 |
1.1 |
1.1 |
13 |
13 |
28 |
640 |
1 |
3 |
1.4 |
1.1 |
1.1 |
0.8 |
13 |
10.1 |
26.3 |
580 |
1/0 |
1/0 |
1.4 |
1.4 |
1.1 |
1.1 |
14 |
14 |
30.2 |
760 |
1/0 |
2 |
1.4 |
1.4 |
1.1 |
0.8 |
14 |
10.9 |
28.3 |
660 |
2/0 |
2/0 |
1.4 |
1.4 |
1.1 |
1.1 |
15 |
15 |
32.3 |
900 |
2/0 |
1 |
1.4 |
1.4 |
1.1 |
1.1 |
15 |
13 |
31 |
820 |
3/0 |
3/0 |
1.4 |
1.4 |
1.1 |
1.1 |
16.2 |
16.2 |
34.9 |
1100 |
3/0 |
1/0 |
1.4 |
1.4 |
1.1 |
1.1 |
16.2 |
14 |
33.5 |
870 |
4/0 |
4/0 |
1.4 |
1.4 |
1.1 |
1.1 |
17.6 |
17.6 |
37.9 |
1320 |
4/0 |
2/0 |
1.4 |
1.4 |
1.1 |
1.1 |
17.6 |
15 |
36.3 |
1180 |
250 |
250 |
1.7 |
1.7 |
1.7 |
1.7 |
20.2 |
20.2 |
43.5 |
1660 |
250 |
3/0 |
1.7 |
1.4 |
1.7 |
1.1 |
20.2 |
16.2 |
41.1 |
1420 |
350 |
350 |
1.7 |
1.7 |
1.7 |
1.7 |
22.8 |
22.8 |
49.1 |
2200 |
350 |
250 |
1.7 |
1.7 |
1.7 |
1.7 |
22.8 |
20.2 |
47.4 |
2000 |
500 |
500 |
1.7 |
1.7 |
1.7 |
1.7 |
25.8 |
25.8 |
55.6 |
2950 |
500 |
350 |
1.7 |
1.7 |
1.7 |
1.7 |
25.8 |
22.8 |
53.6 |
2650 |